Abstract

This study investigates the development and performance of an ANFIS-controlled Unified Power Quality Conditioner (UPQC) integrated into a solar photovoltaic-battery islanded microgrid for voltage regulation, harmonic mitigation, transient stability, and active-power balancing in the Tende-Ama Ogu/Bolo distribution system, Rivers State, Nigeria. The study first assessed the solar energy resource at Tende-Ama Community using Global Horizontal Irradiance (GHI) data obtained from the NASA POWER database for January 2024 to August 2026. An average daily GHI of 4.13 kWh/m²/day was obtained, with PV capacity factors of 62.79%, 60.24%, and 60.19% for the assessed 2024, 2025, and 2026 periods, respectively. A MATLAB/Simulink model of the solar-battery islanded microgrid was subsequently developed, comprising a PV array, MPPT-controlled boost converter, DC-AC inverter, BESS with bidirectional boost-buck converter, balanced load, and nonlinear rectifier load. Load-flow analysis of the Tende-Ama Ogu/Bolo distribution system established the baseline voltage profile under heavy loading and identified Bus 5, Bus 10, Bus 13, Bus 14, and Bus 18 as voltage-weak buses, with voltage magnitudes of 93.25%, 92.77%, 93.50%, 91.59%, and 90.72%, respectively. A UPQC was then integrated at the point of interconnection to provide series and shunt compensation. Harmonic assessment showed that the total harmonic distortion of 20.62% was reduced to 1.15% following UPQC compensation. Under transient voltage disturbances, the UPQC dynamically compensated for voltage sag and swell while maintaining a stable load voltage. Under heavy loading, integration of the ANFIS-controlled UPQC improved all bus voltages to within the 0.95–1.05 pu acceptable operating range, with the previously weak buses improved to 99.327%, 99.091%, 99.945%, 99.500%, and 99.536%, respectively. The findings demonstrate that the integrated ANFIS-controlled UPQC and coordinated PV-BESS control strategy provides an effective approach for improving voltage regulation, mitigating harmonic disturbances, supporting transient stability, and maintaining active-power balance in a solar-battery islanded microgrid.

Keywords

ANFIS controller, DC-AC inverter, load flow, MATLAB/Simulink, microgrid, MPPT-controlled boost converter, photovoltaic (PV)-battery

References

[1] Akinyele T, Adeyemi A, Olanrewaju O. Design and performance analysis of a solar–wind–diesel hybrid energy system in rural Nigeria. Renewable Energy. 2022;18(8):745–756.

[2] Bajaj M, Singh AK. Grid integrated renewable DG systems: a review of power quality challenges and state-of-the-art mitigation techniques. International Journal of Energy Research. 2020;44(1):26–69.

[3] Dandoussou A, Kenfack P. Fuzzy logic control of an automatic changeover for the management of a grid-connected photovoltaic system. International Transactions on Electrical Energy Systems. 2023;4(3):1–13.

[4] Echalih S, Abouloifa A, Lachkar I, El Aroudi A, Hekss Z, Giri F, Al-Numay MS. A cascaded controller for a grid-tied photovoltaic system with three-phase half-bridge interleaved buck shunt active power filter: hybrid control strategy and fuzzy logic approach. IEEE Journal on Emerging and Selected Topics in Circuits and Systems. 2022;12(1):320–330.

[5] Ekeriance ED, Braide SL, Wegwu TA. Performance analysis of a solar-based stability enhancement using interline power flow controller (IPFC). European Journal of Advances in Engineering and Technology. 2026;13(4):7–17.

[6] Jayaswal K, Palwalia DK. Role of reliability assessment in Si-based non-isolated DC-DC power electronic converters. Materials Today: Proceedings. 2022;60:1113–1119.

[7] Jianjun G, Dianguo X, Hankui L, Maozhong G. Unified power quality conditioning (UPQC): the principle, control and application. In: Proceedings of the Power Conversion Conference (PCC-Osaka 2002). 2002. [Pages to be supplied]

[8] Lee K, Kum D. The impact of energy dispatch strategy on design optimization of hybrid renewable energy systems. In: IEEE Milan PowerTech. 2024:1–6.

[9] Nwaigwe KN, Mutabilwa P, Dintwa E. An overview of solar power (PV systems) integration into electricity grids. Materials Science for Energy Technologies. 2019;2(3):629–633.

[10] Rani P, Arora VP, Sharma NK. An overview of integration of PV systems into electric grids. IOP Conference Series: Materials Science and Engineering. 2022;1228(1):012017.

[11] Raj H, Jaiswal S, Maheshwari A. Flow direction algorithm-based optimal power flow for isolated microgrids integrated with renewable energy sources. Wind Engineering. 2025;9(5):82–92.

How to cite this paper

YARHERE, Anthony Kevwe , Dr. E.C. Obuah , Dr. E.D. Ekeriance "Adaptive Neuro-Fuzzy Inference System (ANFIS)-Based Controller for Unified Power Quality Conditioning (UPQC) in Islanded Microgrid" Iconic Research And Engineering Journals Volume 10 Issue 5 2026 Page 3770-3789 https://doi.org/10.64388/ire1725278
YARHERE, Anthony Kevwe , Dr. E.C. Obuah , Dr. E.D. Ekeriance "Adaptive Neuro-Fuzzy Inference System (ANFIS)-Based Controller for Unified Power Quality Conditioning (UPQC) in Islanded Microgrid" Iconic Research And Engineering Journals, vol. 10, no. 5, Nov. 2026, doi: https://doi.org/10.64388/ire1725278
YARHERE, Anthony Kevwe , Dr. E.C. Obuah , Dr. E.D. Ekeriance (2026). Adaptive Neuro-Fuzzy Inference System (ANFIS)-Based Controller for Unified Power Quality Conditioning (UPQC) in Islanded Microgrid. Iconic Research And Engineering Journals, 10(5). doi: https://doi.org/10.64388/ire1725278
YARHERE, Anthony Kevwe , Dr. E.C. Obuah , Dr. E.D. Ekeriance "Adaptive Neuro-Fuzzy Inference System (ANFIS)-Based Controller for Unified Power Quality Conditioning (UPQC) in Islanded Microgrid" Iconic Research And Engineering Journals, vol. 10, no. 5, Nov. 2026. Crossref, https://doi.org/10.64388/ire1725278
@article{1725278,
      author = {YARHERE, Anthony Kevwe , Dr. E.C. Obuah  , Dr. E.D. Ekeriance },
      title = {Adaptive Neuro-Fuzzy Inference System (ANFIS)-Based Controller for Unified Power Quality Conditioning (UPQC) in Islanded Microgrid},
      journal = {Iconic Research And Engineering Journals},
      year = {2026},
      volume = {10},
      number = {5},
      pages = {3770-3789},
      issn = {2456-8880},
      url = {https://www.irejournals.com/formatedpaper/1725278.pdf},
      abstract = {This study investigates the development and performance of an ANFIS-controlled Unified Power Quality Conditioner (UPQC) integrated into a solar photovoltaic-battery islanded microgrid for voltage regulation, harmonic mitigation, transient stability, and active-power balancing in the Tende-Ama Ogu/Bolo distribution system, Rivers State, Nigeria. The study first assessed the solar energy resource at Tende-Ama Community using Global Horizontal Irradiance (GHI) data obtained from the NASA POWER database for January 2024 to August 2026. An average daily GHI of 4.13 kWh/m²/day was obtained, with PV capacity factors of 62.79%, 60.24%, and 60.19% for the assessed 2024, 2025, and 2026 periods, respectively. A MATLAB/Simulink model of the solar-battery islanded microgrid was subsequently developed, comprising a PV array, MPPT-controlled boost converter, DC-AC inverter, BESS with bidirectional boost-buck converter, balanced load, and nonlinear rectifier load. Load-flow analysis of the Tende-Ama Ogu/Bolo distribution system established the baseline voltage profile under heavy loading and identified Bus 5, Bus 10, Bus 13, Bus 14, and Bus 18 as voltage-weak buses, with voltage magnitudes of 93.25%, 92.77%, 93.50%, 91.59%, and 90.72%, respectively. A UPQC was then integrated at the point of interconnection to provide series and shunt compensation. Harmonic assessment showed that the total harmonic distortion of 20.62% was reduced to 1.15% following UPQC compensation. Under transient voltage disturbances, the UPQC dynamically compensated for voltage sag and swell while maintaining a stable load voltage. Under heavy loading, integration of the ANFIS-controlled UPQC improved all bus voltages to within the 0.95–1.05 pu acceptable operating range, with the previously weak buses improved to 99.327%, 99.091%, 99.945%, 99.500%, and 99.536%, respectively. The findings demonstrate that the integrated ANFIS-controlled UPQC and coordinated PV-BESS control strategy provides an effective approach for improving voltage regulation, mitigating harmonic disturbances, supporting transient stability, and maintaining active-power balance in a solar-battery islanded microgrid.},
      keywords = {ANFIS controller, DC-AC inverter, load flow, MATLAB/Simulink, microgrid, MPPT-controlled boost converter, photovoltaic (PV)-battery},
      month = {November},
      doi = {https://doi.org/10.64388/ire1725278}
  }